* Conductor |
: |
Plain Annealed copper wire class 2 according to IEC 60228 |
* Insulation |
: |
Extruded XLPE ( Crosslinked Polyethylene) |
* Individual Screen |
: |
Helically Overlapped Polyester Tape
Tinned Annealed Copper Wire 0.5 mm2 ( 20/0.18 mm )
Helically Overlapped Single Coated Aluminium Tape contacted with drain wire
Helically Overlapped Polyester Tape |
* Overall Screen |
: |
Helically Overlapped Polyester Tape
Tinned Annealed Copper Wire 0.5 mm2 ( 20/0.18 mm )
Helically Overlapped Single coated Aluminium Tape contacted with drain wire
Helically Overlapped Polyester Tape |
* Inner Sheath |
: |
Extruded PVC Flame Retardant ( Black ) |
* Metallic Sheath |
: |
Extruded Lead Sheath} |
* Separation Sheath |
: |
Extruded PVC Flame Retardant ( Black ) |
* Armour |
: |
Galvanized Steel Wire |
* Outer Sheath |
: |
Extruded PVC Flame Retardant ( Black or requested by customer ) |
Pair Identification : |
|
|
* 1 Pair |
: |
Black and white |
* Multi Pair |
: |
Black and white with numbering |
Amount of halogen acid gas |
: |
Max 17% ( IEC 60754-1) |
Limiting oxigen index ( LOI ) |
: |
Min 30% ( IEC 60332-3 annex B ) |
Sunlight resistance |
: |
UL 1581 section 1200 |
Oil resistance |
: |
ICEA S-82-552 |
Flame Retardant |
: |
IEC 60332-1 |
Flame Propagation |
: |
IEC 60332-3 cat. A, B, C |
Nominal Voltage |
: |
300 V dan 500 V |
Insul Resistance |
: |
Min. 1000 MOhm/km |
Test Voltage |
: |
300 V : 1000 V/1 min
500 V : 2000 V/1 min |
Screen Resistance |
: |
Min. 1 MOhm/km |
Min.Bending Radius |
: |
6 x OD ( fixed installation ) |
Temperature Rating |
: |
-40° C to 70° C |
Symbol
|
:
|
CU/XLPE/IS-OS/LS/SWA/PVC or P1 T3 IS-OS
|
Applicable Standard |
: |
Multipair XLPE Insulated Instrumentation Cable
Flame Retardant, UV Resistant
According to BS EN 50288-7 : 2005
Voltage Designation 300 V & 500 V |
P1 T3 IS-OS |
: |
XLPE Insulated, Individual and Overall Collective Screen, Lead Sheath, Armoured
Other Specification are available on request |
Application |
: |
Suitable for connecting instrument and control system for analogue or digital signal transmission.These cables shall not be connected directly to mains electricity supply or other low impedance sources and not designed to be used for power supply.Not suitable for direct buried applications. |