Produk Kami

N2XFGbY

TANTANGAN ANDA ADALAH PROGRESS KAMI

Other specification are available on request.

Identification of Cores

Twin-Cores               : Light-Blue, Black

Three-Cores             : System I

                                 Green with yellow stripe (G/Y), Blue, Brown, System 0

                                 Brown, Black, Grey

Four-Cores                : System I

                                 Green with yellow stripe (G/Y), Brown, Black, Grey

                                 System 0

 


Five-Cores                 : System I
                                   Green with yellow stripe (G/Y), Brown, Black, Grey 
                                   System 0
                                   Blue, Brown, Black, Grey, Black

 

Other colour are available on request


Construction    :
Conductor        :  Annealed Copper
Insulation         :  Extruded XLPE
Inner Sheath     : Extruded PVC
Armouring         : Flat Steel Wire and Tape
Outer Sheath    : Extruded PVC

 

Special Features on Request :


Oil Resistance
Flame Retardant Cat. A,B,C
Flame Retardant Non Category
Nylon Coated

 

CONSTRUCTION

No. of core Size Conductor Wall Thickness Approx Overall Diameter  Approx Net. Weight Standard Length Packing
Construction No. of Wire Insulation Sheath
2 16 re/rm 7 0.7 1.8 22.0 1037 500 Drum
2 25 re/rm 7 0.9 1.8 25.4 1395 500 Drum
2 35 re/rm 7 0.9 1.9 27.8 1739 500 Drum
2 50 re/rm 19 1.0 2.0 32.6 2178 500 Drum
2 70 re/rm 19 1.1 2.2 36.8 7024 500 Drum
2 95 re/rm 19 1.1 2.2 42.2 9056 500 Drum
2 120 re/rm 37 1.2 2.2 45.5 10696 500 Drum
2 150 re/rm 37 1.4 2.2 49.7 12967 250 Drum
2 185 re/rm 37 1.4 2.5 61.0 14989 250 Drum
2 240 re/rm 61 1.4 2.5 67.6 17503 250 Drum
2 300 re/rm 61 1.6 2.7 73.2 17988 250 Drum

 

CHARACTERISTICS

No. of Core Size Resistance at 20% Current Carrying Capacity at 30° C* Short Circuit Current at 1 Sec. AC Voltage Test
Conductor  Insulation In Ground  In Air
mm² 0hm/km M. 0hm. Km Ampere kA kV/5 min
2 16 0.15 1.100 128 113 2.27 3.5
2 25 0.727 1.100 167 150 3.55 3.5
2 35 0.524 1.000 201 186 4.97 3.5
2 50 0.387 900 239 226 7.10 3.5
2 70 0.268 900 295 290 9.94 3.5
2 95 0.193 800 355 353 13.49 3.5
2 120 1.153 800 404 413 17.04 3.5
2 150 0.124 800 458 468 21.30 3.5
2 185 0.0991 800 516 540 26.27 3.5
2 240 0.0754 700 600 590 34.08 3.5
2 300 0.0601 700 695 645 42.60 3.5

 note : If conditions are different. The labuled current ratings should be multiplied by rating factors as show in table pages 51-56

Symbol :
Size Ranged : 2 x 16 ... 300mm²
5 x 10 ... 50mm²
3 x 1.5 ... 300mm²
mm²
4 x 10 ... 300mm²
Applicable Standard :

Other Specification are available on request

Application : Indoor and Outdoor, Installation direct bureal Preferably use where considerable mechanical stress must be envisaged
Belum ada data
Belum ada data

Untuk mengunduh detail produk anda harus masuk atau jika anda belum akun silahkan mendaftar terlebih dahulu, Klik disini untuk mendaftar